Fire Safety Equipment Upgrade Case Studies

Property managers, owners and shop operators understand that fire safety must comply with requirements, yet improvements are often delayed because the starting point is unclear or there are concerns about disruption and cost. A Fire Safety Direction, an insurer's enquiry, missing licence documents or a small fire can reveal the value of acting earlier. Prepared by Fire Station, Hong Kong fire extinguisher specialists, this article uses six scenario-based examples typical of Hong Kong premises to explain the original problems, applicable requirements, improvement steps and outcomes, followed by an action checklist you can adapt.

The following cases are based on the usual situation in Hong Kong's malls, workshops, parking lots, offices, restaurants and old buildings, and are handled anonymously and in a simplified manner. It is used as an illustration of how to improve thinking; Elements of the statute are attached and the actual requirements are based on the documents issued by the Fire Services Department in respect of individual locations. Fire Station actually serves as Customer Fire Safety Case Studies.

6 cases at a glance (30 seconds to read all)

  • Market space: Insurance queries reveal fire extinguishers without annual inspection for more than a decade, recycling old cartridges, changing new ones, establishing records.
  • Plant building: Chapter 636, Fire Safety Directive Emergency lighting along escape routes and exit lights.
  • Multi-layer parking spaces: fire extinguishers are covered by miscellaneous items, poorly marked, repositioned, stickers added, electric vehicles charged floors pressed.
  • Small- and medium-sized enterprises write the building: after moving the fire extinguisher was blocked and the employees were not aware of the use of the equipment, the inspection was done in conjunction with the staff training.
  • New restaurant: The application for license is to be made in conjunction with the Fire Services Department regulations for water extinguishers, CO2, heavy fire blankets, UL-300 systems.
  • Old Building Law Corps: Chapter 572 directs the improvement of the public sector, fire extinguishers, emergency lighting, exit directions.

Contents

  1. Case I: Replacement of expired fire extinguishers at the mall, due for renewal of insurance queries
  2. Case II: Plant building equipped with emergency lights in accordance with fire safety instructions
  3. Case III: Repositioning fire extinguishers and charging floors of electric vehicles
  4. Case IV: Small and medium-sized enterprises move their offices, equipment upgrades to match staff training
  5. Case V: New restaurant set up by the fire regulations for the food license plate.
  6. Case VI: Improvement of the utility component of the old building under Chapter 572
  7. Cross-cutting issues in six cases
  8. List of actions: How to use your location
  9. What can Fire Station do to help?
  10. Common problems FAQ

Case I: Replacement of expired fire extinguishers at the mall, due for renewal of insurance queries

Background

The owner of a fashion shop in a medium-sized mall has taken over the seat for more than five years. Two fire extinguishers are hanging inside the house, and they are intact.

Problems identified

  • The two fire extinguishers did not have any recent professional inspection records, nor did they have any FS251.
  • The pressure table pointer deviates from the green range.
  • The bottom of the barrel had visible rust and had been moved and removed during the renovation.
  • One of them is an old model and the label does not see whether it is approved by the Fire Services Department.

Elements of legislation

  • The Fire Services Department requires the fire extinguisher owner to arrange for a minimum annual inspection by a registered fire-fighting operator and a five-year hydraulic test.
  • 14 days after the contractor has completed the inspection issue the FS 251 certificate and deliver it to the Fire Services Department.
  • All hand-held fire extinguishers must be authorized by the Fire Services Department to be supplied or sold in Hong Kong.
  • Fire extinguishers in the Tenant Units, which are based on licence plates or legislation, are generally the responsibility of the occupants, depending on the lease.

Steps for improvement

  1. On-site assessment: Identification of space, layout, entry/exit location and type of cargo.
  2. The existing fire extinguishers were counted and it was confirmed that both had to be replaced.
  3. 2 kg dry powder extinguisher, a close door, a close back door.
  4. On the day the new cylinder is deliveredFire Extinguisher Recycling Serviceand mounted with a sticker.
  5. FS251 is issued by a level III fire operator and the owner keeps a certificate and a list of fire extinguishers.

Result

The owner of the store has a clear annual check date and certificate, which can be submitted immediately upon renewal.

The number of configurations of the same business is the same as the number of places that can be used to Fire Extinguisher Planning for Shops & Offices.

Case II: Plant building equipped with emergency lights in accordance with fire safety instructions

Installation of fire extinguishers and fire-fighting equipment in factory buildings - Fire Station
Live installation of fire-fighting equipment at the industrial unit

Background

The owner receives a fire safety directive, one of which is to install emergency lighting within a specified range to ensure that there is enough light to escape when power is out or fire alarms.

Problems identified

  • There are no emergency lights in the unit and no exit signs at the top of the exit.
  • There was an old emergency light in the corridor, but the battery was broken and the power was not on at the time of the blackout.
  • Employees are not aware of two exits and are accustomed to using only the main door.

Elements of legislation

  • The Fire Safety (Industrial Buildings) Ordinance (chap. 636), which came into force on 19 June 2020, applies to industrial buildings built or first presented on or before 1 March 1987, where the Fire Services Department and the Buildings Department can issue fire safety instructions to owners for improvement.
  • The Fire Services Department Code of Minimum Fire Protection Devices and Equipment requires emergency lighting systems to be in compliance with B S 5266-1 and B S EN 1838, which are automatically opened when power is interrupted and the entire building and all access routes to the ground must be installed.
  • The exit sign font is not less than 125 mm and is installed on the floor from 2 to 2.5 m and located directly above the exit doorway.
  • Emergency lighting is a fire-fighting device that is inspected every 12 months by the registered contractor.

Steps for improvement

  1. Field survey of working areas, storage areas, two exits and the route to the stairs.
  2. The requirements of the fire safety instructions are verified on a point-by-point basis.
  3. Designed for escape Emergency Lighting & Exit Signs: main route, corner, two exits.
  4. Two exit doors are marked with exit lights and directional lights at the corner of the corridor.
  5. Inspection of fire extinguishers in the unit: 5kg dry powder in the storage area and 2kg carbon dioxide in the vicinity of the electric switch box.
  6. Upon completion, certificates were issued by the contractor and improvements were reported to the Fire Services Department by the owner.

Result

The manager also runs an evacuation drill to explain the new emergency light and the two exits. The employee says he knows which way to go, even if the light goes out suddenly.

The full configuration of the works can be seen Fire Extinguishers for Car Parks & Industrial Buildingsthe requirements for emergency lighting are detailed Emergency Lighting & Exit Signs Explained.

Case III: Repositioning fire extinguishers and charging floors of electric vehicles

Background

An old multi-layer parking lot has been set up as required in the early years. Over the years, berthings have been modified, fenced, storage space added, and parts of the fire extinguishers, although "still " , are piled with miscellaneous items, marked vaguely, and the driver is not aware of them.

Problems identified

  • Some of the annual fire extinguishers were qualified, but the front was covered by garbage cans and temporary structures.
  • The new fence and billboard cover the original logo.
  • The driver went straight out and had no idea where the fire extinguisher was.
  • Levels to be charged are not configured as new.

Elements of legislation

  • The Department of Labour ' s Fire at Work Guidelines require fire-fighting equipment to be placed in a position where it is easily accessible and unobstructed.
  • The Fire Services Department code and circulars: a parking lot with electrical vehicle charging facilities, on the floor where the facility is installed, shall be provided with an additional dry powder or carbon dioxide extinguisher at each larynx setting site; additional requirements such as fire detection systems (in a boundary of 230 square metres) and emergency switches with firefighters.

Steps for improvement

  1. The fire extinguishers were reprogrammed according to traffic, traffic, exits, stairs and throats.
  2. Covered fire extinguishers will be moved to the post or to the side of the throat, close to the exit and management booth.
  3. Every fire extinguisher plus a stick er with arrows and arrows so far as the driver can see.
  4. Add an additional 5 kg dry powder or 5 kg carbon dioxide extinguisher for each larynx level on the charger floor, with CO2 next to the charger.
  5. The Service classifies the front line of fire extinguishers as "no stacking" and includes them in the monthly inspection form.
  6. Powerhouses with CO2 near control cabinets, public places and fire-fighting sand drum s.

Result

The Director of the garage, at the same location as the new driver’s briefing, will indicate the location of the fire extinguisher.

Detailed regulations for the parking lot can be found Fire Extinguishers for Car Parks & Industrial Buildings; actual service customers in the garage can see Customer Fire Safety Case Studies.

Case IV: Small and medium-sized enterprises move their offices, equipment upgrades to match staff training

Background

A small and medium-sized enterprise of about 30 people moved into the new building, where the fire extinguishers from the old office were to be renovated and added to the building’s original equipment. Until HR arranged for the first fire drill to discover the problem.

Problems identified

  • Some of the fire extinguishers are covered by the new private file cabinet and are not easily accessible.
  • There are fire extinguishers whose annual inspection is about to expire and whose stickers are vague.
  • The new unit has a server room but no CO2 extinguisher.
  • New staff members are completely unaware of the fire extinguishers and are even less aware of their use.

Elements of legislation

  • The Occupational Safety and Health Ordinance requires employers to provide information, guidance, training and supervision.
  • The Department of Labour directs employees to know the location of fire extinguishers and the methods used.
  • The Fire Services Department ' s Maintenance of Equipment for Handheld Fire extinguisher Training Course and Guidance for Mentors ' Qualifications: The physical demonstration should be conducted by the Fire Safety Ambassador, a registered contractor of level 3 or with firefighting experience; the training fire extinguisher will be supplemented by a test for a level 3 contractor.

Steps for improvement

  1. On-site assessments of new layouts are conducted to check the number, location and condition of extinguishers.
  2. The shielded fire extinguishers were adjusted to the entrance, the printing area and the tea room.
  3. Add 2kg CO2 extinguisher to the server room door.
  4. Expired fire extinguisher replacement, old cartridge Fire Extinguisher Recycling Service.
  5. On the day the installation took place, the employees were shown the same position as "drive, aim, click, sweep".
  6. HR sent two colleagues to attend the fire department community emergency pioneer course and became a company fire liaison officer.
  7. HR collates a "Bedroom Fire Safety Profile" which is used when new colleagues enter the job.

Result

HR has a reusable profile and training record.

A list of the building's fire safety checks can be consulted for the checking of the officeOffice Fire Safety Checklistdetails of the training arrangements Fire Extinguisher & Staff Fire Safety Training.

Case V: New restaurant set up by the fire regulations for the food license plate.

Background

A teahouse about 80 square metres is open, and you can apply for a license plate from the Food and Economics Department. The Fire Services Department has a fire safety code that lists the hand-held fire-fighting equipment to be placed with the kitchen automatic fire-fighting system.

Problems identified

  • Fire extinguishers purchased online did not meet the specifications specified by the Fire Services Department.
  • Light fire blankets are to be used, but only heavy equipment is required by the Fire Services Department.
  • The location of the furnace is not known to be equipped with an automatic fire suppression system.

Elements of legislation

  • The fire safety regulations issued by the Fire Services Department in respect of food consumption indicate the type, specification and quantity of equipment approved for hand-held fire suppression, such as 9 litres of water extinguishers, 4.5 kg of carbon dioxide extinguishers, 1. 44 square metres of blankets for fire suppression; generally, a blanket for fire suppression is provided for each furnace.
  • An automatic fire suppression system meeting UL-300 standards shall normally be installed, except for automatic flowers spilling, in a common cooking cooker with a frying position.
  • Fire Services Department Fire Circular No. 11: Only heavy (BS 7944) and reusable fire blankets are first accepted as equipment required by the Fire Services Department.
  • The stand-alone emergency lighting system of the licensed premises is maintained for at least 2 hours.

Steps for improvement

  1. The required documents issued by the Fire Services Department are submitted to the vendor for quotations to the specified specifications.
  2. Seat room with 9L water extinguisher, kitchen with CO2 extinguisher and heavy fire blanket.
  3. Installation of the UL-300 automatic fire suppression system by the registered contractor at the site of the furnace.
  4. The kitchen entrance is equipped with fire-fighting blankets, which are not to be mounted directly above the stove.
  5. Installation of emergency lights and exit lights.
  6. Certificates are issued by the contractor to accompany the application for licence plates.

Result

The fire department has been approved once, and the licence plate has not been delayed because the equipment does not conform to the specifications.

The kitchen fireproofing is detailed Fire Blankets & Kitchen Fire Safetythe catering configuration is detailed Fire Extinguisher Planning for Shops & Offices.

Case VI: Improvement of the utility component of the old building under Chapter 572

Background

There are several fire extinguishers in the stairwells, some of which are rusty.

Problems identified

  • The years of stairwell fire extinguishers are unknown, rusty and no annual check-ups are recorded.
  • There was no emergency lighting in the corridors and stairs and it was completely black when the power went out.
  • There are no signs at the exit.
  • The back stairs were blocked by household chores and old homes.

Elements of legislation

  • The Fire Safety (Buildings) Ordinance (chap. 572) applies to buildings used for general purposes on or before 1 March 1987, with a schedule indicating that the owner may be required to provide or improve emergency lighting in the public sector.
  • Fire Services Department Circular No. 3/2026: Accepts an item-networked fire detection system and hand-held fire extinguishers as an alternative to the six -stor ey or less target buildings regulated by Chapter 572 comply with the requirements for a larynx system and a hand-held fire alarm system.
  • Ineffective fire extinguishers with chemical substances or pressures are chemical wastes that are to be recovered by suppliers or contractors.

Steps for improvement

  1. The Mission checked the dates of the instructions and contacted the registered fire-fighting contractors to assess them with accredited persons.
  2. The rusty fire extinguishers of the same year are Fire Extinguisher Recycling Service, and each stairwell platform is replaced with a 5kg dry powder extinguisher, plus a sticker.
  3. The corridor, the stairs and the lobby are Emergency Lighting & Exit Signsand exit lights on the exit door.
  4. In the case of larynx and alarm system requirements, examine with the contractor the applicability of the alternative to Circular No. 3/2026.
  5. The Directorate clears the stairwells and posts a warning to the household.
  6. The completion certificate was obtained, the declaration was made to the Fire Services Department and the annual inspection date was set.

Result

The administration budget is supplemented by an annual check and no further "remediation" is expected.

Other fire equipment in the building can be found Common Fire Safety Equipment in Hong Kong Buildings; misunderstandings in the legislation are detailed Hong Kong Fire Safety Regulations: Common Myths.

VII. COMMON ISSUES IN THE SIX CASES

Cross-cutting issues It's a few cases. Direction of the resolution
There's a device, but there's no annual check.The mall, the old building, the French.Annual contractor inspection, FS251, maintenance list
Places are covered, unmarked.Garage, officeMove to the spot, sticker, row "no stack" range, monthly check.
We don't know where to start when we get the instructions.The factory building, the old building.Check the duration of the project, find the registered contractor and the approved person, file the completion report.
Type without riskoffice (no CO2 in server room), restaurant (light fire blanket)Select the model by type of fire alarm and fire department.
No emergency lighting.The factory building, the old building.Installation of emergency lights and exit lights in accordance with the code, to be checked annually
I don't know what to do with it.Garage, officeTraining, exercises, induction, fire liaison
I thought "home" was a card-holder.Dining room.Configure by required documents issued by the Fire Services Department
I don't know what to do with it.AllRecycled to suppliers or contractors, no rear stairs

VIII. LIST OF ACTIONS: HOW TO USE YOUR PLACE

Steps Do what? References
1. Count wellNumber of fire extinguishers, emergency lights, exit lights, location, type, capacity, annual inspection date on siteFire Extinguisher Inspection & Replacement
2. Depending on the situationPressure meters, silos, labels, pins; emergency lights pressed test buttons; were not coveredOffice Fire Safety Checklist
3. Reconciling requirementsDo you have fire safety instructions, license regulations, MS requirements, insurance requirements?Hong Kong Fire Safety Regulations: Common Myths
4. Finding professional evaluationSubmission of lists, same requirements documents to suppliers or registered contractorsContact Fire Station
5. Do it once.Replacement, addition, transfer, recovery of old cartridges, emergency lighting, FS251 completed on the same dateFire Extinguisher Recycling Service
6. Teaching peopleDemonstration of use at installation; organization of training and exercises; introduction of new recruitsFire Extinguisher & Staff Fire Safety Training
7. TimingMonthly inspections, annual inspections, water pressure tests every five years, written into the calendar and budgetFire Extinguisher Servicing or Replacement

How can Fire Station assist?

Fire Station is a fire extinguisher shop in Tsuen Wan and a fire-fighting equipment provider, and we can all work together to improve the above six scenes:

2kg dry powder extinguishers - common for upgrading commercial and offices

2kg dry powder extinguisher

The first choice is to trade, write and replace the clinic.

View Products
5kg Dry powder extinguisher - Garageman ' s common portion of old building

5kg dry powder extinguisher

Garage, workshop and building stairwells.

View Products
2kg CO2 extinguisher - server room power room

2kg CO2 extinguisher

Server room, electrical room, near charger.

View Products

Actual clients served include leading malls and parking lots, trust parking lots, speed transport, etc. as detailedCustomer Fire Safety Case Studies. Query pleaseWhatsApp 96309976Call.3464 3987Or go.Contact Fire StationKeep information on low places.

Common issues FAQ

What should be done to receive instructions on fire safety improvements?

Check the duration of the projects specified in the instructions and then contact the registered fire operator to evaluate with the accredited person and design the programme in accordance with the requirements of the Minimum Fire Devices and Equipment Code, etc., Once completed, the certificate is obtained and declared to the Fire Services Department, after which an annual inspection is scheduled for each year. Old-style industrial buildings are regulated by Chapter 636 and old-style integrated-use buildings by Chapter 572.

The insurance company asked for fire equipment records. What should be prepared?

The list of fire extinguishers (location, type, capacity, date of production), the most recent FS251 certificate, annual review and water pressure test records, replacement and recycling records, and staff training and exercise records are generally included.

Garages filled with electric charge points, fire extinguishers?

In accordance with the Fire Services Department code and circulars, the parking lot with the electrical vehicle charging facility should be provided with an additional dry powder or carbon dioxide extinguisher at each of the larynx locations on the floor where the facility is installed. Additional requirements, such as fire detection systems and emergency switches for firefighters, should be assessed by the registered operator together with accredited persons.

Can you move the old fire extinguisher directly to the new unit when you move the building?

It is possible to move, but it is necessary to re-evaluate the number of places according to the size, layout and risk of the new unit, to confirm that the annual inspection of each fire extinguisher is still valid, in good condition, and to update the list with FS251.

You're going to have to prepare some fire-fighting equipment for a restaurant with a license plate?

The Fire Services Department will issue fire safety regulations for individual meals, specifying authorized hand-held firefighting equipment to be placed, such as 9 litres of water extinguishers, 4.5 kilograms of carbon dioxide extinguishers and 1.44 square metres of fire blankets; Ordinary cooking stoves are typically equipped with automatic fire suppression systems that meet UL-300 standards. Fire blankets are of the heavy type accepted by the Fire Services Department.

The F.L.A. of the old building has been instructed to improve the fire-fighting equipment in the public sector.

Chapter 572 applies to buildings for combined use on or before 1 March 1987 and improvements may include emergency lighting of the public part, etc. The Mission should check the content of the instructions with the time frame and contact the registered fire operator to assess the corridors, stairs, fire extinguishers in the lobby, emergency lighting and exit instructions. Upon completion, the certificate is obtained and declared. The six-storey or below target buildings can be alerted to the Internet-based fire detection system with hand-held fire extinguisher alternatives, which is accepted by Fire Services Department Circular No. 3/2026.

Replacement of old fire extinguisher points?

Fire Services Department means a chemical waste in which an invalid fire extinguisher still contains chemical substances or memory pressure, which should be recovered by the supplier or registered fire-fighting contractor, and may not be disposed of or stacked in the back stairwell.

How can Fire Station help upgrade the equipment?

Fire Station provides fire extinguishers approved by the Fire Services Department and has packaged basic deliveries, which can be arranged for on-site assessment, recommended type of placement, mounted stickers, demonstration usage, recycling of old cartridges, etc. FS251 certificates issued by a level III fire operator; Emergency lighting lamps are also available for retailing with exit lights and for year-on-year testing. Telephone 3464 3987 ,WhatsApp 96309976 。

The common denominator of the six cases is simple: the problem is not "no equipment", but no one is really looking at it, the placement is not ideal, the instructions are not starting, the people are not aware of it. Starting today, counting your fire extinguishers with emergency lighting, checking your requirements, then replacing, repositioning, recycling, training and so forth. "Safety" is a practical arrangement that has a date, a record and a responsible person. Needing assistance, welcome Contact Fire Station, we'll follow your actual environment, regulations and budget proposals for the improvement of qualified fire extinguish ers with fire-fighting equipment.

You want to upgrade fire suppression equipment for your mall, shop, parking lot or office?

Fire Station provides on-site assessments, fire department accreditation for fire extinguishers, delivery, installation, recycling, and FS251 certificates.